How TO SET POWER METER PM 5350 WITHOUT USING VT (Voltage Transformer)
Electrical Instrument - On this occasion I Mas Lubis, will post an article on how to set the PM 5350 power meter where in the installation does not use Voltage Transformer (VT) but directly connect to the 400 Volt AC busbar.
HOW TO SET PM 5350
Here are the rare settings of PM 5350
1. Press the right-hand button to search for the MAINT menu
2. Press MAINT
3. Press SETUP
4. Enter password 0000
5. Press METER
6. Press BASIC
7. Press the bottom direction to select
- Circuit Mode: Normal
- Power System: 3PH4W Wye Gnd
- VT Connect: Direct con
- CT on Terminal: I1 I2 I3
- CT Primary (A): fills 250 if the installed CT Ratio is 250/5A
- Secundari CT: fill 5 if the installed CT Ratio is 250/5A
- Sys Frequency (HZ): 50
- Phase Rotation: ABC
So my post about how TO SET POWER METER PM 5350 WITHOUT USING VT (Voltage Transformer), hopefully useful for all of you, if there is less or need improvement in the writing of this article please write in the comments column so that we can fix it quickly. Thank you